INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 7500TL
101/
148
P099
Range
0 ÷ 32000
0.0 ÷ 320.0 s
Maximum
Frequency Reset
Time
Default
10 (Italy), 10 (Spain), 3000 (Germany)
Level
ADVANCED
Address
699
Function
Time during which the reset condition of the maximum frequency must be
maintained to reset the grid maximum frequency fault.
P100
Range
-300 ÷ -10
[-3 ÷ -0.1] Hz
Minimum
Frequency Trip
Threshold
Default
-30 (Italy),
-200 (Spain),
-250
(Germany)
Level
ADVANCED
Address
700
Function
This parameter defines the maximum value of the frequency offset in
respect to the nominal value at which the grid minimum frequency fault
trips.
P101
Range
1000 ÷ 1006
1.000 ÷ 1.006
Minimum
Frequency
Release Ratio
Default
1002
Level
ADVANCED
Address
701
Function
Sets the ratio between the trip frequency of the minimum frequency fault
and the value at which the minimum frequency fault is reset.
P102
Range
40 ÷ 5000
0.040 ÷ 5.000 s
Minimum
Frequency Trip
Time
Default
50 (Italy), 3000 (Spain), 150 (Germany)
Level
ADVANCED
Address
702
Function
Time during which the trip condition of the minimum frequency must be
maintained to prompt the activation of the grid minimum frequency fault.
P103
Range
0 ÷ 32000
0.0 ÷ 320.0 s
Minimum
Frequency Reset
Time
Default
10 (Italy), 10 (Spain), 3000 (Germany)
Level
ADVANCED
Address
703
Function
Time during which the reset condition of the minimum frequency must be
maintained to reset the minimum frequency fault.
P114
Range
0 ÷ 1
0: Inactive
1: Active
Minimum
Percentage of
DV606 Instant
Voltage
Default
15
Level
ADVANCED
Address
714
Function
Threshold percentage for instant voltage fault.