INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 7500TL
83/
148
R003
Range
1 ÷ 7
1: 1200 bps
2: 2400 bps
3: 4800 bps
4: 9600 bps
5: 19200 bps
6: 38400 bps
7: 57600 bps
Baud Rate
Default
6
6: 38400 bps
Level
ADVANCED
Address
590
Function
Sets the baud rate, expressed in bits per second, for the serial link.
R004
Range
1 ÷ 10000
1 ÷ 10000 ms
Time Added to
4byte–time
Default
2
2 ms
Level
ADVANCED
Address
591
Function
Sets the limit time after which, if no more characters are received from the
serial link, the message sent from the Master to the inverter is considered
as finished.
R005
Range
0 ÷ 65000
0 ÷ 6500.0 s
Watchdog Safety
Time
Default
0
0.0 s
Level
ADVANCED
Address
592
Function
This parameter sets the limit time after which, if no more characters are
received from serial link 0 (9-pole, male D connector), alarms
A061
(Serial
Link n. 0 WDG Alarm) trips.
If R005 is set to zero, alarm
A061
is disabled.
R006
Range
0 ÷ 3
0: Disabled 1 Stop–bit
1: Disabled 2 Stop–bit
2: Even (1 Stop–bit)
3: Odd (1 Stop–bit)
Parity Bit
Default
1
1: Disabled 2 Stop–bit
Level
ADVANCED
Address
593
Function
Sets whether the parity bit is used or not when creating the Modbus
message via serial link.