4.3.7.1. Status Conditions
The status conditions of the inverter are as follows:
Status message
M089
Description
DISCONNECT SWITCH
OFF
101
The integrated disconnect switch is in OFF position. The inverter is
waiting for the disconnect switch to switch to ON.
STOP
102
The inverter is stopped. The inverter is in STOP status when:
o
it is at its first startup;
o
the
STOP
button has been pressed from the graphic
interface module.
The inverter quits this status only after the
START
button is pressed
from the front panel.
PROTECTIVE DEVICE
TEST
104
The inverter is testing the integrated grid coupling device.
POWER DELIVERY
106
The inverter is operating in parallel to the grid and is delivering
power.
While the inverter is in this status, the
Additional Info
field
displays
the power being delivered.
DECOUPLING
107
The inverter has opened the integrated grid coupling device and is
no longer operating in parallel to the grid.
INITIALIZATION
108
The inverter is initializing.
LIMITATION
109
The inverter is limiting. Limiting causes are the inverter internal
temperature (
M057
) and the heatsink temperature (
M059
).
SENSOR TEST
111
The inverter is testing the integrated current sensors.
INSULATION TEST
112
The inverter is performing the earth insulation test of the PV field.
RELAY TEST
113
The inverter is performing the insulation test of the integrated grid
coupling device.
ALARM
116
An alarm has tripped, that cannot be autoreset.
While the inverter is in the Alarm status, the
Additional Info
field
displays the code of the alarm tripped.
ALARM (R)
117
An autoresettable alarm has tripped.
While the inverter is in the Alarm (R) status, the
Additional Info
field
displays the code of the alarm tripped.
RESET
118
The alarm has been reset by the user or by the autoreset function.
The inverter is restarting.
START TIMEOUT
120
The field voltage detected by the inverter is higher than the value
set in
P020
. The inverter is waiting for the time set in
P021
to
elapse before connecting in parallel to the grid and start producing
power.
While the inverter is in the Start Timeout status, the
Additional Info
field shows the timeout countdown.
MIN GRID STAND-BY
121
The grid voltage detected by the inverter is lower than the minimum
allowable value.
MAX GRID STAND-BY
122
The grid voltage detected by the inverter is higher than the
maximum allowable value.
FREQ GRID STAND-BY
123
The grid frequency detected by the inverter is out of the allowable
range.
SYNCHRO STAND-BY
124
The inverter is synchronising with the grid.
GRID TIMEOUT
125
The grid values are in the allowable range. The inverter is waiting
for the preset timeout (5s) to elapse before connecting in parallel to
the grid and start producing power.
While the inverter is in the Grid Timeout status, the
Additional Info
field shows the timeout countdown.