SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
12/
148
DANGER
CONNECTION TO THE PV FIELD – When exposed to solar radiation,
the photovoltaic panels produce DC voltage that is applied to the
inverter.
ELECTRIC SHOCK HAZARD
–
Do not touch the electric parts of the
inverter and do not operate on the inverter when it is powered. Always wait
at least 20 minutes from the instant when the DC and AC supply is
removed from the inverter before carrying out any operation, because
electric energy is accumulated inside the inverter.
Do not operate on the equipment when it is powered.
Before operating on the electric connections, remove both DC and AC
voltage from the equipment and wait at least 20 minutes.
EXPLOSION AND FIRE
–
The risk of explosion and fire may exist if the
equipment is installed in presence of flammable fumes. Do not install the
equipment where there is a risk of explosion and fire.
CAUTION
Do not connect supply voltages which exceed the rated voltage. If voltage
exceeding the rated value is applied, the internal circuits may be damaged.
In the event of installation in presence of flammable and/or explosive
substances, please consult the relevant applicable standards.
In the event of an alarm, consult section 4.3.6 Alarms Menu. Only restart
the equipment after the problem has been rectified.
Do not carry out isolation tests between the power terminals or between the
control terminals.
Make sure that the screws on the connection terminal boards have been
properly tightened.
Observe the environmental requirements for installation.
DANGER
Certain parts of the product (side walls, heatsink and reactors) may reach
temperatures as high as 100 °C. Take all the necessary precautions to
avoid burns.
DANGER
Do not remove the inverter lid during installation
. Removing the lid may
affect the IP rating of the inverter and may damage the internal parts.
Removing the lid voids the inverter warranty.