SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
30/
148
3.4.5. Fiscal Seal
A fiscal seal may be applied to the inverter, where required. The seal may be applied through the special
slots on both sides of the product cover and enclosure. Remove the connector protective cover to gain
access to the slots. Figure 17 shows the location of the slots.
Figure 17: Slots for the application of the fiscal seal
3.5.
Commissioning
NOTE
The SUNWAY M XS inverter is factory-set with a set of parameters fitting
most applications; therefore, no parameter modification is generally
required.
Always carry out the Quick Configuration procedure of the touchscreen
display (see section 4.3.5.1).
1)
Make sure that the inverter connections to the PV field and the grid are correct.
2)
Reassemble the connector protective cover, if previously removed.
3)
Connect the inverter to the grid by closing the grid-side switch.
The SUNWAY M XS inverters are supplied from the grid. Once the connection to the grid is complete,
press the WAKE UP button to power on the product.