SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
122/
148
Status message
M089
Description
OVERLOAD
126
The current delivered by the inverter has been higher than the
nominal current for an exceedingly long time. The Overload
condition will last for 15 minutes, then normal operation will be
resumed.
While the inverter is in the Overload status, the
Additional Info
field
shows the timeout countdown.
WEAK SOLAR RADIATION
130
The grid voltage is lower than the value set in
P020
. The Weak
Solar Radiation condition will last until the field voltage exceeds the
set threshold.
MAX FIELD STAND-BY
131
Field voltage out of the allowable range.
POWER OFF
134
The inverter is powering off after it has been detecting a field
voltage lower than the value set in
P020
for the time set in
P041
.
Table 29: Status messages for the SUNWAY M XS inverters
4.3.7.2. Status Info
The
Status Info
field lists important operating conditions for the inverter operation:
•
GRID OK, when the grid voltage is in the allowable range for the inverter operation;
•
FIELD OK, when the field voltage is in the allowable range for the inverter operation (voltage
exceeding the value set in
P020
);
•
MPPT ON, when the MPPT function is activated;
•
RUN, when the inverter is producing energy.
4.3.7.3. Warnings
Warnings are service messages addressed to the user and are displayed in the
Status Info
field
in the
inverter Status window. When a warning appears, the Status window will include the “Warning” wording
followed by the active warnings.
Figure 73: Example of a warning
NOTE
Warnings are neither protections nor alarms and are not stored to the Alarm
History.