SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
92/
148
P041
Range
0 ÷ 600
0 ÷ 600 min
Power Off Delay
Default
15
15 min
Level
ADVANCED
Address
641
Function
Time when the inverter is waiting for a field voltage value exceeding
P020
;
when that time is over, the inverter is powered off.
Menu
POWER BALANCE
Submenu
Access
Level
Action
R052 – POWER BALANCE
Displays the current status of the Power
Balance functionality
ADVANCED
Activates a list window. Select one of the following:
−
DISABLED
−
ENABLED
P400 – PHASE
Displays the value currently set for the Power
Balance function phase
ADVANCED
Activates a list window. Select one of the following:
−
R
−
S
−
T
Table 20: Tools menu, Advanced Configuration > Inverter > Power Balance
R052
Range
0 ÷ 1
0: Disabled
1: Enabled
Power Balance
Default
0
0: Disabled
Level
ADVANCED
Address
190
Function
Enables the Power Balance functionality. The Power Balance functionality
requires the inverters to be connected to an external CAN bus. Details on
the Power Balance functionality are given in section 5.3.
P400
Range
1 ÷ 3
1: R
2: S
3: T
Phase
Default
1
1: R
Level
ADVANCED
Address
540
Function
Phase for the Power Balance algorithm. The phase is to be set up during
the commissioning of the product based on the connection of the product
to the PV plant. If the phase setting is incorrect, this will adversely affect
the Power Balance functionality by tripping the safety devices or reducing
the delivered power.