Error
Code
Contents
Measure
Product op. in
error condition
Error Type
Outdoor unit /
Comp. / Ind. unit
475
Outdoor fan 2 error
Check th einput power connection status
Check the connection status of the motor and
the outdoor unit PCB
Check the indoor/outdoor unit fuse
Operation off
Self diagnostic
error
554
Gas leak error
Check the coolant charging status
Check the indoor EVA sensor
Check if the outdoor unit service value is open
Check that the indoor/outdoor installation
pipe/wiring are correct
Operation off
Self diagnostic
error
556
Capacities not matched
Check the option code of the indoor unit
Operation off
Outdoor unit
protection control
error
601
Communication error be-
tween the indoor unit and
wired remote controller
Check the connection wire between the indoor
unit and the wired remote controller
Operation off
Wired remote
controller error
602
Communication error
between the Master
and Slave wired remote
controllers
Check the option switch for defining the
master and slave (only one master and one
slave can exist)
Normal opera-
tion
Wired remote
controller error
606
COM1/COM2 cross
installation error
Check that wired remote controller is con-
nected to the COM2 terminal of the indoor unit
Normal opera-
tion
Wired remote
controller error
607
Communication error
between the Master
and Slave wired remote
controllers.
Check the option switch for defining the
master and slave (only one master and one
slave can exist)
Normal opera-
tion
Wired remote
controller error
Fault Codes