Fault Codes
Error
Code
Contents
Measure
Product op. in
error condition
Error Type
Outdoor unit /
Comp. / Ind. unit
101
Indoor unit communica-
tion error
Check the communication cable of indoor
unit. Check the DC output voltage at the com-
munication terminal.
Operation off
Communication
error
102
Indoor unit/outdoor unit
communication time-out
error: errors in more than
6 packets
Check the outdoor communication cable
connection. Check DC output voltag and the
communication terminal.
Operation off
Communication
error
121
Indoor temperature sen-
sor (open/short error)
Check indoor unit room temperaute sensor.
Check indoor unit PCB connector CN41
(White)
Operation off
Indoor sensor error
122
Indoor unit Eva in sensor
(Open/Short)
Check indoor unit pipe sensor. Check indoor
PCB connector CN41 (White)
Operation off
Indoor sensor error
128
Indoor unit Eva in sensor
disconnection
Check the disconnection of indoor unit pipe
sensor.
Operation off
Indoor sensor error
153
Indoor floating switch
secondary detection
Check indoor unit float sensor. Check indoor
PCB connector CN5 (black)
Operation off
Self diagnostic
error
202
Indoor/outdoor commu-
nication error (1 min)
Check the communication connection
between indoor and outdoor units. Check the
power line and communication cable connec-
tion status.
Operation off
Communication
error
203
Communication error
between indoor/outdoor
INVIMAIN <-> MICOM
(1 min)
Check MAIN MICOM
Check INVERTER MICOM
Operation off
Communication
error
221
Outdoor temperature
sensor error
Check sensor connection status
Check sensor location
Check sensor resistance
Operation off
Outdoor sensor
error
237
COND temperature sen-
sor error
Check sensor connection status
Check sensor location
Check sensor resistance
Operation off
Outdoor sensor
error
251
[Inverter] Emission tem-
perature sensor error
Check sensor connection status
Check sensor location
Check sensor resistance
Operation off
Outdoor sensor
error