CO5´: System-wide functions (all systems)
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01
AA1 reverse
0
All
CO5´ > F01 - 0: 0 V/0 % = Valve CLOSED/pump OFF
CO5´ > F01 - 1: 0 V/0 % = Valve OPEN/pump with max. de-
livery rate
Function block parameters:
Zero: 0 to 50 % (0 %)
07 AI1 Zero shift
0
All*
CO5´ > F07 - 0
Function block parameters:
Zero: 5 to 20 % (5 %)
F Function block number, WE Default setting, Anl System code number
CO6: Modbus (all systems)
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01
Modbus
1
All
CO6 > F01 - 1: Modbus active
02
16-bit address
0
All
CO6 > F02 - 1: Modbus 16-bit addressing (only with
CO6 > F01 - 1)
CO6 > F02 - 0: 8-bit addressing
03 Modem
function
0
All
CO6 > F03...F06 is required to configure the error message
transfer to a connected Modbus/GPRS gateway (1402-0701).
04
Automatic
modem
configuration
0
All
05 Lock dial-up to
building
automation
system
0
All
06 Dial-up to
building
automation
system also to
indicate that
an error has
been remedied
0
All
07 Monitoring
0
All
CO6 > F07 - 1: Reset all even bits to 'autonomous' when there
is no communication (only when CO6 > F01 - 1)
08
Text message
0
All
CO6 > F08 is required to configure the error message transfer
to a connected Modbus/GPRS gateway (1402-0701).