24
EB 5573 EN
Start-up
3.2
Activating and deactivating functions
A function is activated or deactivated in the associated function block. 0 to 24 at the top of
the display represent the function block numbers. When a configuration level is opened, the
activated function blocks are indicated by a black square on the right-hand side below the
function block number. For more details on function blocks, see section 13.1.
The functions are grouped by topics:
−
CO1:
HC1 (heating circuit 1)
−
CO2:
HC2 (heating circuit 2)
−
CO4:
DHW circuit
−
CO5:
System-wide
−
CO6:
Modbus communication
1.
Turn the rotary switch to (parameter and configuration level).
Reading:
0 0 0 0
2.
Enter valid key number [
q
].
3. Confirm key number [
Û
].
Reading:
PA_
4.
Select configuration level [
q
].
5. Open configuration level [
Û
].
6. Select function block [
q
].
Activated function blocks are marked '- 1'.
Deactivated function blocks are marked '- 0'.
7. Activate editing mode for the function block [
Û
].
blinks.
8.
Activate function block [
q
].
Reading:
F__ - 1
An activated function block is indicated by a black square below (right) the function
block number at the top of the controller display.
or:
Deactivate function block [
q
].
Reading:
F__ - 0