EB 5573 EN
119
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
12
Creep feed
rate limitation
0
Not Anl
1.9
CO5 > F12 - 1: Creep feed rate limitation
Selection:
bin (input terminals 04/12), AnA (input RüF1)
Function block parameters when 'bin' is selected:
bE = 1, bE = 0 (bE = 1)
14
Operation UP1
0
3.0, 16.x
CO5 > F14 - 1: feeder pump UP1 also starts to operate to cov-
er the demand of HC2.
15 Release
controller at
input BI1
0
All
With CO5 > F15 - 1 setting: FG1 has no function
Select:
BI = 1, BI = 0 (BI = 1)
16 Return flow
temperature
limitation with
P algorithm
0
All
CO5 > F16 - 1: Return flow temperature limitation only with pro-
portional component
19 Temperature
monitoring
0
All
CO5 > F19 - 1: Temperature monitoring active
20
Sensor
calibration
1
All
CO5 > F20 - 1: Set all sensor calibration values
CO5 > F20 - 0: Delete all sensor calibration values
21
Lock manual
level
0
All
CO5 > F21 - 1: controller runs in automatic mode in
switch
position
22
Lock the rotary
switch
0
All
CO5 > F22 - 1: Rotary switch without any function. It is still
possible to enter the key number.
23 Outdoor
temperature as
0 to 10 V
signal
0
All
CO5 > F23 - 1: Outdoor temperature received as 0 to 10 V
signal (AE) or sent (AA), terminals 11/12
Function block parameters:
Direction: AE, AA (AE)
Lower transmission range: –50.0 to +100.0 °C (–20.0 °C)
Upper transmission range: –50.0 to +100.0 °C (50.0 °C)
F Function block number, WE Default setting, Anl System code number