14
EB 5573 EN
Operation
2.6 Setting the times-of-use
Three times-of-use can be set for each day of the week.
Parameters
Default
1)
Value range
Period/day
1-7
1-7, 1, 2, 3, 4, 5, 6, 7 with 1-7 daily, 1 = Monday, 2 =
Tuesday, …, 7 = Sunday
Start first time-of-use
06:00 00:00 to 24:00 h; in steps of 15 minutes
Stop first time-of-use
22:00 00:00 to 24:00 h; in steps of 15 minutes
Start second time-of-use
22:15 00:00 to 24:00 h; in steps of 15 minutes
Stop second time-of-use
22:15 00:00 to 24:00 h; in steps of 15 minutes
Start third time-of-use
--:--
00:00 to 24:00 h; in steps of 15 minutes
Stop third time-of-use
--:--
00:00 to 24:00 h; in steps of 15 minutes
1)
Default settings applicable to the heating circuits
Proceed as follows:
1.
Turn the rotary switch to (times-of-use).
blinks.
In systems with only one control circuit (e.g. system Anl 1.0), steps 2 to 5 (to select the
control circuit and configure the DHW circuit) are not required.
In systems Anl 1.5 and 1.9, only the DHW circuit is controlled. As a result, steps 2 and 3
(to select the control circuit) are not required.
2.
Select the control circuit for which the time-of-use is to be programmed.
1:
Heating circuit 1
2:
Heating circuit 2
3:
DHW heating/circulation pump
Only those control circuits are available for selection which can be controlled by the se-
lected system.
3. Confirm the selected control circuit [
Û
].
If control circuit 1 or 2 has been selected, steps 4 and 5 are not required.
4.
Configure DHW circuit [
q
]:
DHW heating
Circulation pump (DHW)
5. Confirm setting [
Û
].