EB 5573 EN
17
Operation
2.8
Activating extended information level
After activating the extended information level, the following information can be read after
the listed data points:
−
Capacity
−
Flow rate
V
·
−
Public holidays
(can be changed, see section 2.8.1)
−
Vacations (can be changed, see section 2.8.2)
−
Valve positions
−
Switching states of the binary inputs
−
InFo 2: After confirmation [
Û
] the following values are shown one after the other:
Controller ID
Memory left in data logging module (see
section 10.3)
255
Operating hours of solar circuit pump (see
section 7.4)
Opening the extended information level
1.
Turn the rotary switch to (parameter and configuration level).
Reading:
0 0 0 0
, blinks.
2.
Enter key number 1999 [
q
].
3. Confirm key number [
Û
].
Reading:
0 0 0 0
4.
Turn the rotary switch back to normal switch position (information level).
−
The additional information is hidden when the key number 1999 is entered again.
−
The key number 1999 cannot be used to change the controller configuration and
parameterization. A separate key number exists for configuration and parameterization
(see section 3).
Note