EB 5573 EN
69
Functions of the heating circuit
Depending on the room sensor, the controller switches off the heating system up to one hour
before the time-of-use ends. The controller chooses the deactivation time such that the room
temperature does not drop significantly below the desired value until the time-of-use ends.
During the advance heating period and the premature deactivation of the heating system, the
or
icon blink on the display.
Outside the times-of-use, the controller monitors the 'Night set point' (reduced room tempera-
ture). When the temperature falls below the night set point, the controller heats with the max.
flow temperature until the measured room temperature exceeds the adjusted value by 1 °C.
−
Direct sunshine can cause the room temperature to increase and thus result in the prema
-
ture deactivation of the heating system.
−
When the room temperature decreases while the heating system is shortly outside its times-
of-use, this can prematurely cause the controller to heat up to the 'Day set point'.
Functions
WE
Configuration
Room sensor RF1/RF2
0
CO1, 2 > F01 - 1
Outdoor sensor AF1
1
CO1 > F02 - 1
Optimization
0
CO1, 2 > F07 - 1
Parameters
WE
Switch position: value range
Day set point
20.0 °C
: 0.0 to 40.0 °C
Night set point
15,0 °C
: 0.0 to 40.0 °C
6.9 Flash adaptation
To ensure that the controller reacts immediately to room temperature deviations during rated
or reduced operation, the function block setting CO1, 2 > F09-1 needs to be made. The
heating is then always switched off as soon as the room temperature exceeds the 'Day set
point' or 'Night set point' by 2 °C.
Heating first starts again when the room has cooled off and the room temperature is 1 °C
above the 'Set point'. The flow temperature set point is corrected if the 'Cycle time' or 'Gain
KP' are set to a value other than 0. The 'Cycle time' determines the intervals at which the flow
temperature set point is corrected by 1 °C. A 'Gain KP' set to a value other than 0 causes a
direct increase/decrease in flow temperature set point when a sudden deviation in room tem-
perature arises. We recommend a 'Gain KP' setting of 10.0.
Note
Summary of Contents for TROVIS 5573
Page 144: ...144 EB 5573 EN Key number 1732...