EB 5573 EN
123
Appendix
Display reading
Parameter name
Value range (default setting)
Four-point characteristic
Point 1: outdoor temperature
Outdoor temperatures of points 2, 3 and 4 are marked by squares
under the numbers 2, 3 and 4.
–50.0 to +50.0 °C
(pt. 1: –15.0 °C, pt. 2: –5.0 °C, pt. 3: 5.0 °C, pt. 4: 15.0 °C)
When CO1, 2 > F04 - 1
(pt. 1: 5.0 °C, pt. 2: 15.0 °C, pt. 3: 25.0 °C, pt. 4: 30.0 °C)
Four-point characteristic
Point 1: flow temperature
Flow temperatures of points 2, 3 and 4 are marked by squares un-
der the numbers 2, 3 and 4.
–5.0 to +150.0 °C
(pt. 1: 70.0 °C, pt. 2: 55.0 °C, pt. 3: 40.0 °C, pt. 4: 25.0 °C)
When CO1, 2 > F04 - 1:
(pt. 1: 20.0 °C, pt. 2: 15.0 °C, pt. 3: 10.0 °C, pt. 4: 5.0 °C)
Four-point characteristic
Point 1: reduced flow temperature
Reduced flow temperatures of points 2, 3 and 4 are marked by
squares under the numbers 2, 3 and 4.
–5.0 to +150.0 °C
(pt. 1: 60.0 °C, pt. 2: 40.0 °C, pt. 3: 20.0 °C, pt. 4: 20.0 °C)
When CO1, 2 > F04 - 1:
(pt. 1: 30.0 °C, pt. 2: 25.0 °C, pt. 3: 20.0 °C, pt. 4: 15.0 °C)
Four-point characteristic
Point 1: return flow temperature
Return flow temperatures of points 2, 3 and 4 are marked by
squares under the numbers 2, 3 and 4.
5.0 to 90.0 °C
(points 1 to 4: 65.0 °C)