62
EB 5573 EN
Functions of the heating circuit
Parameters
WE
Parameter level: value range
Flow temperature
Point 1
Point 2
Point 3
Point 4
70.0 °C
55.0 °C
40.0 °C
25.0 °C
PA1, 2: –5.0 to +150.0 °C
Reduced flow temperature
Point 1
Point 2
Point 3
Point 4
60.0 °C
40.0 °C
20.0 °C
20.0 °C
PA1, 2: –5.0 to +150.0 °C
Return flow temperature
Points 1 to 4 65.0 °C
PA1, 2: 5.0 to 90.0 °C
Min. flow temperature
20.0 °C
PA1, 2: –5.0 to +150.0 °C
Max. flow temperature
90.0 °C
1)
PA1, 2: 5.0 to +150.0 °C
1)
With CO1, 2 > F05-1 the following
applies:
Max. flow temperature: 5.0 to 50.0 °C (50.0 °C)
6.2 Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed set
point. Outside the times-of-use, the controller regulates to a reduced flow temperature. Set
the desired rated flow temperature as 'Day set point' and the reduced flow temperature as
'Night set point'.
Functions
WE
Configuration
Outdoor sensor AF1
1
CO1 > F02 - 0
Parameters
WE
Switch position: value range
Day set point
50.0 °C
: Min. to max. flow temperature
Night set point
30.0 °C
: Min. to max. flow temperature
Parameters
WE
Parameter level: value range
Min. flow temperature
20.0 °C
PA1, 2: –5.0 to +150.0 °C
Max. flow temperature
90.0 °C
PA1, 2: 5.0 to 150.0 °C
A fixed set point control in heating circuit HC2 can only be configured with CO2 > F02 - 0
when CO1 > F02 - 0 is also configured since heating circuit HC2 configured with CO2 >
F02 - 0 only uses the measured outdoor temperature provided by heating circuit HC1.
Note