EB 5573 EN
21
Operation
2.9 Entering day and night set points
For the heating circuits, the desired room temperatures during the day ('Day set point') and
during the night ('Night set point') can be entered into the controller. In the DHW circuit, the
temperature you wish the DHW to be heated to can be set.
Switch position
Parameters
WE
Value range
Day set point HC1, HC2
20 °C –5.0 to +150.0 °C
DHW temperature set point
60 °C Min. to max. DHW temperature
Switch position
Parameters
WE
Value range
Night set point HC1, HC2
15 °C –5.0 to +150.0 °C
DHW temperature set point
40 °C Min. to max. DHW temperature
Proceed as follows:
1.
Turn the rotary switch to the required data point.
for the day set point and DHW temperature set point
for the night set point and DHW temperature sustaining value
blinks.
In systems Anl 1.0, 1.9 and 3.5, the current set point is directly displayed. The following
steps 2 and 3 (to select the control circuit) are not required.
2.
Select the control circuit for which the set point is to be set [
q
]:
1:
Heating circuit 1
2:
Heating circuit 2
3:
DHW circuit
Only those control circuits are available for selection which can be controlled by the se-
lected system.
3. Confirm the selected control circuit [
Û
].
Reading: Current set point
4.
Adjust the set point [
q
].
5. Turn the rotary switch back to normal switch setting (information level).