Start-up
Return flow sensor RüF
Storage tank sensor SF1
Storage tank sensor SF2
Storage tank sensor of solar circuit SF2
9. Display measured value [
Û
].
"°C" blinks.
10.
Correct measured value [
q
].
Read the actual temperature directly from the thermometer at the point of measurement
and enter this value as the reference temperature.
11.
Confirm corrected measured value [
Û
].
Proceed in the same manner to calibrate further sensors.
12.
Select
End
[
q
].
13. Turn the rotary switch back to normal switch setting (information level).
3.5
Resetting to default settings
All parameters set over the rotary switch as well as parameters in the PA1, PA2 and PA5 pa-
rameter levels can be reset to their default settings (WE) except for the maximum flow tem-
perature and the return flow temperature limits in PA1 and PA2.
1.
Turn the rotary switch to (parameter and configuration level).
Reading:
0 0 0 0
2.
Enter key number 1991 [
q
].
3. Confirm key number [
Û
].
The controller loads the default settings.
Reading:
0 0 0 0