EB 5573 EN
113
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
18
Request max.
flow set point
using
0 to 10 V
Output terminals
11/12
0
All*
CO1 > F18 - 1: the standardized signal output (terminals
11/12) is not available anymore as a control output. The maxi-
mum flow set point (with boost, if applicable) is demanded as
a 0 to 10 V signal at the standardized signal output.
Function block parameters:
Lower transmission range: 0.0 to 150.0 °C (0.0 °C)
Upper transmission range: 0.0 to 150.0 °C (120.0 °C)
Boost flow temperature demand: 0 to 30.0 °C (0 °C)
20
External
demand for
heat due to
insufficient
heat supply
0
All
CO1 > F20 - 1: Demand of an external heat source
21
Speed
reduction of
charging pump
0
16.x
CO1 > F21 - 1: Temperature-based adaptation of the delivery
rate of the charging pump
Function block parameters:
Start speed reduction - SF2 limit: 5.0 to 90.0 °C (40.0 °C)
Stop speed reduction - SF2 limit: 5.0 to 90.0 °C (50.0 °C)
Minimum speed: 0 to 50 % (20 %)
22
SLP depending
on return flow
temperature
0
16.x
CO1 > F22 - 1: Storage tank charging pump not ON unless
return flow hot
23 Differential
temperature
control
0
System Anl
1.0, 16.0
only
CO1 > F23 - 1: Activation of differential temperature control
Function block parameters:
Set point of differential temperature control: 0.0 to 50.0 °C
(20.0 °C)
KP (influence factor): 0.1 to 10.0 (1.0)
Minimum speed: 0 to 100 % (20 %)
F Function block number, WE Default setting, Anl System code number
CO2: HC2 · Heating circuit 2 (systems Anl 3.x, 4.x, 10.0, 16.6)*
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01
Room sensor
RF2
0
All*
CO2 > F01 - 1: Temperature reading and FG2 input for
Types 5244 and 5257-5 or 5257-51 Room Panels active
03 Return flow
sensor RüF2
1
10.x
CO2 > F03 - 1: Sensor and limitation function active
Function block parameters:
KP (limiting factor): 0.1 to 10.0 (1.0)
0
3.0, 4.x,
16.6