136
EB 5573 EN
Appendix
F
Function block parameters
CO1
CO2
Value range
03 - 1 KP (limiting factor)
0.1 to 10.0
05 - 1 Start temperature
20.0 to 60.0 °C
05 - 1 Hold (days)
0 to 10 days
05 - 1 Temp. rise/day
0.0 to 10.0 °C
05 - 1 Maximum temperature
25.0 to 60.0 °C
05 - 1 Hold (days)
0 to 10 days
05 - 1 Temp. reduction/day
0.0 to 10.0 °C
09 - 1 Cycle time
0/1 to 100 min
09 - 1 KP (gain)
0.0 to 25.0
12 - 1 KP (gain)
0.1 to 50.0
12 - 1 Tn (reset time)
1 to 999 s
12 - 1 TV (derivative-action time)
0 to 999 s
12 - 1 TY (valve transit time)
15 to 240 s
12 - 0 Hysteresis
1.0 to 30.0 °C
12 - 0 Min. ON time
0 to 10 min
12 - 0 Min. OFF time
0 to 10 min
13 - 1 Max. system deviation
3.0 to 10.0 °C
14 - 1 Binary input
bE = 1, bE = 0
16 - 1 Lower transmission range
0.0 to 150.0 °C
16 - 1 Upper transmission range
0.0 to 150.0 °C
17 - 1 Binary input
–
bE = 1, bE = 0
18 - 1 Lower transmission range
–
0.0 to 150.0 °C
18 - 1 Upper transmission range
–
0.0 to 150.0 °C
18 - 1 Boost flow temperature demand
–
0.0 to 30.0 °C
21 - 1 Start speed reduction
5 to 90 °C
21 - 1 Stop speed reduction
5 to 90 °C
21 - 1 Min. speed signal
0 to 10 V
23 - 1 Set point of differential
temperature control
0.0 to 50.0 °C
23 - 1 KP (influence factor)
0.1 to 10
23 - 1 Minimum speed
0 to 100 %