Annex A (configuration instructions)
Menu
Adjustment range/values/description
Signal source
2.4.x.12
Enter the signal source on which the 4 to 20 mA signal is
based
▪
Unknown (default)
▪
Filling level
▪
Pressure
▪
Temperature
Measured value
2.4.x.14
Reading of the current measured value in the selected unit
Unit
2.4.x.15 Unit in which the measured value is to be indicated.
▪
Selectable units:
% · kg · Nm³ · L · ft³ · lbs · mbar · bar · kPa · psi · mmH
2
O ·
cmH
2
O · mH
2
O · inH
2
O · °C · °F · K
Lower measuring range
value
2.4.x.16
Determine the lower limit of the measuring range at 4 mA
(depending on the selected unit)
Upper measuring range
value
2.4.x.17
Determine the upper limit of the measuring range at 20 mA
(depending on the selected unit)
Event: Broken cable
2.4.x.18 Activates or deactivates the event for a detected cable
breakage at the input of the AI option module. The event is
activated when the signal falls below the switching threshold of
0.2 mA.
▪
ON (default)
▪
OFF
Event: Residual current
2.4.x.19 Activates or deactivates the event for a detected residual
current violation at the input of the AI option module. The event
is activated when the signal falls below the switching threshold
of 3.6 mA or exceeds 21.0 mA.
▪
ON (default)
▪
OFF
Limit 1
2.4.x.20
Activate/deactivate limit 1
▪
ON (default)
▪
OFF
Mode
2.4.x.21 An upper limit can be determined with 'Max. contact' and a
lower limit with 'Min. contact' for limit 1.
▪
Max. contact
▪
Min. contact
Summary of Contents for Media 7 5007-1
Page 6: ...6 EB 9510 EN...
Page 14: ...1 8 EB 9510 EN...
Page 20: ...2 6 EB 9510 EN...
Page 68: ...7 12 EB 9510 EN...
Page 76: ...8 8 EB 9510 EN...
Page 90: ...13 2 EB 9510 EN...
Page 92: ...14 2 EB 9510 EN...
Page 97: ...EB 9510 EN 15 5...
Page 98: ...15 6 EB 9510 EN...
Page 99: ...EB 9510 EN 15 7...
Page 100: ...15 8 EB 9510 EN...
Page 101: ...EB 9510 EN 15 9...
Page 102: ...15 10 EB 9510 EN...
Page 123: ......