16-16
EB 9510 EN
Annex A (configuration instructions)
Menu
Adjustment range/values/description
Error message E3
4.2.4
Determines whether an error message is issued in case of
condensed state (E3) (see page 16-15).
▪
No
▪
Yes
Diagnostic data
4.3
Operation duration
4.3.1
Reading of the entire operating time of the device
(dd:hh:mm:ss)
Temperature
4.4
Max. temperature inside
device
4.4.1
Activate/deactivate the alarm for the maximum device
temperature in the device.
▪
OFF (default)
▪
On
Limit
4.4.2
Set an upper temperature limit within the specified range. If
the current device temperature is above the adjusted limit, an
error message is generated and displayed. The status
changes to 'Out of specification'.
▪
10 to 70 °C (default: 60 °C)
Min. temperature inside
device
4.4.3
Activate/deactivate the alarm for the minimum device
temperature in the device.
▪
OFF (default)
▪
On
Limit
4.4.4
Set a lower temperature limit within the specified range. If
the current device temperature is below the adjusted limit, an
error message is generated and displayed. The status
changes to 'Out of specification'.
▪
–40 to +10 °C (default: –15 °C)
Filling level events
4.5
Filling limit alarm (SCN)
4.5.1
Activate/deactivate the permissible filling level
▪
ON
▪
OFF (default)
Pre-alarm
4.5.2
Activate/deactivate the pre-alarm when the filling level falls
below the limit.
▪
ON (default)
▪
OFF
Summary of Contents for Media 7 5007-1
Page 6: ...6 EB 9510 EN...
Page 14: ...1 8 EB 9510 EN...
Page 20: ...2 6 EB 9510 EN...
Page 68: ...7 12 EB 9510 EN...
Page 76: ...8 8 EB 9510 EN...
Page 90: ...13 2 EB 9510 EN...
Page 92: ...14 2 EB 9510 EN...
Page 97: ...EB 9510 EN 15 5...
Page 98: ...15 6 EB 9510 EN...
Page 99: ...EB 9510 EN 15 7...
Page 100: ...15 8 EB 9510 EN...
Page 101: ...EB 9510 EN 15 9...
Page 102: ...15 10 EB 9510 EN...
Page 123: ......