10-4
EB 9510 EN
Servicing
Table 10-1:
Recommended inspection and testing
Inspection and testing
Action to be taken in the event of a negative re-
sult
Check the markings, labels and nameplates on
the differential pressure meter for their readability
and completeness.
Contact SAMSON when nameplates or labels are
damaged, missing or incorrect to renew them.
Clean any inscriptions that are covered with dirt
and are illegible.
Check the differential pressure meter to ensure it
is mounted properly.
Tighten the any loose mounting screws.
Check the measuring lines.
Tighten any loose screw fittings.
Replace any leaking lines.
Check the power lines.
Tighten any loose cable glands.
Make sure that the stranded wires are pushed into
the terminals and tighten any loose screws on the
the terminals.
Renew damaged lines.
Check error messages on the display (indicated
by the , , and icons).
Troubleshooting (see the 'Malfunctions' section).