EB 9510 EN
16-17
Annex A (configuration instructions)
Menu
Adjustment range/values/description
Limit
4.5.3
Set the limit in % (appears as marking 1 on the display).
▪
0.0 to 100.0 %
(default: 30 %)
Main alarm
4.5.4
Activate/deactivate the main alarm when the filling level falls
below the limit.
▪
ON (default)
▪
OFF
Limit
4.5.5
Set the limit in % (appears as marking 2 on the display).
▪
0.0 to 100.0 %
(default: 15 %)
Differential pressure
events
4.6
Filling limit alarm (SCN)
4.6.1
Activate/deactivate the permissible filling level
▪
ON
▪
OFF (default)
Pre-alarm
4.6.2
Activate/deactivate the pre-alarm when the filling level falls
below the limit.
▪
ON (default)
▪
OFF
Limit
4.6.3
Set the limit in % (appears as marking 1 on the display).
▪
0.0 to 100.0 %
(default: 30 %)
Main alarm
4.6.4
Activate/deactivate the main alarm when the filling level falls
below the limit.
▪
ON (default)
▪
OFF
Limit
4.6.5
Set the limit in % (appears as marking 2 on the display).
▪
0.0 to 100.0 %
(default: 15 %)
Pressure sensor events
4.7
Limit 1
4.7.1
Activate/deactivate limit 1
▪
ON (default)
▪
OFF
Summary of Contents for Media 7 5007-1
Page 6: ...6 EB 9510 EN...
Page 14: ...1 8 EB 9510 EN...
Page 20: ...2 6 EB 9510 EN...
Page 68: ...7 12 EB 9510 EN...
Page 76: ...8 8 EB 9510 EN...
Page 90: ...13 2 EB 9510 EN...
Page 92: ...14 2 EB 9510 EN...
Page 97: ...EB 9510 EN 15 5...
Page 98: ...15 6 EB 9510 EN...
Page 99: ...EB 9510 EN 15 7...
Page 100: ...15 8 EB 9510 EN...
Page 101: ...EB 9510 EN 15 9...
Page 102: ...15 10 EB 9510 EN...
Page 123: ......