Start-up and configuration
How to proceed:
1. Press key (in start screen) to go to the main menu.
2.
Select [Pressure span (reference) | 1.9] with
or
key and confirm with
key.
3.
Set the reference pressure (e.g. 10 bar) with
or
key and confirm with
key.
4. Press
to exit the [Pressure span (reference)| 1.9] parameter.
5.
Select [Pressure sensor span | 1.10] with
or
key and confirm with
key.
The current values for the measured value, span and reference are displayed.
6. Press key twice to set the span.
The span setting is active. If it is to be no longer used, it must be reset ([Pressure sensor
span| 1.10] parameter).