MAX100/200-OPERATION Rev200813
75
7. Press the
INCREASE
or
DECREASE
button until 'ADD CALIBRATION POINT' has been selected. Press
the
SELECT
button to add this data as a calibration point. A confirmation dialog box will appear to indicate
this operation was successful. Should the data entry fail, repeat the process from step 6.
8. Pressurize the system to the highest level that can be safely achieved. Be aware of the pressure rating of
all components being used for this calibration. Determine the lowest safe pressuring rating.
Under any
circumstances, do not exceed this pressure rating
.
9. Press the
INCREASE
or
DECREASE
button to move to the pressure value field. Use the
SELECT
button
to increase the digit at the cursor position. Use the
ON/OFF
button to decrease the digit at the cursor position.
Use the
INCREASE
or
DECREASE
button to move the cursor to the next position. Enter the pressure as
measured by the external pressure meter.
10. When the pressure has been entered, press the
INCREASE
or
DECREASE
button until 'ADD CALIBRATION
POINT' has been selected. Press the
SELECT
button to add this data as a calibration point. A confirmation
dialog box will appear to indicate this operation was successful.
11. To finish calibration, press the
INCREASE
or
DECREASE
button until 'SAVE AND RETURN' item is
selected. Press the
SELECT
button to save the calibration data and return to the Maintenance submenu. Or,
press the
ON/OFF
button to cancel the calibration and restore the previous values.
NOTE: Make sure the pressure that was built up in the system is safely relieved before disconnecting
any equipment.