Report Functions
Report feature of the AccuMax system is used to record the consumption of water and foam concentrate by the
system for each incident of system use. Incident data can be reviewed using any AccuMax display module. If needed,
stored data can be exported as a CSV file and saved on an external USB device.
Report recorded for each incident data will contain:
●
Date and time when incident started *
●
Date and time when incident ended *
●
Total volume of water discharged
●
Total volume of foam concentrate used by system
* If date is not set, elapsed time from the system start will be used instead
By default, the last 20 incidents are recorded. Oldest incident will be deleted when the number of incidents
exceeds the default number.
What is AccuMax Use Incident?
An incident is defined as an event when the AccuMax system is used to deliver foam and/or water. A new incident
is created for each power-up of the system. If the system is not used to deliver foam or water during the current power
cycle, the incident data will not be saved.
An incident data recording begins when the AccuMax system detects the system total volume of foam concentrate,
or when the total volume of water begins to increase (while the system is flowing water and/or foam). At that time, the
incident start date/time is recorded. ‘REPORT INCIDENT START’ message will be displayed in the message bar briefly
to indicate the beginning of the recording.
The current Incident’s data is updated and saved when the total volume of foam concentrate and total volume of
water remains unchanged for approximately 10 seconds (system water flow and foam flow are equal to 0). This usually
happens when the system operation has finished. ‘REPORT UPDATED’ message will be displayed in the message bar
briefly to indicate the data was updated.
NOTE: If the AccuMax system operation has resumed, incident data recording will continue.
An incident ends when the system is powered-down. Keep the system powered on for at least 10 seconds after the
AccuMax system has been in use. Within this time, the report data will be updated and saved. Power can be disconnected
as needed.
Creating New Incident Manually
If the AccuMax system is used for more than one fire operation while it remains connected to power, each subsequent
fire operation can be individually recorded by creating a new report incident before the new operation has been started.
This is achieved by reseting all accumulated system totals.
To create a new incident in the Report feature:
1. Make sure foam delivery is turned off on all displays and the system does not see any water flow.
2. Select 'USER SETTINGS' on the main menu. Press the
SELECT
button to access the submenu.
3. Select 'RESET TOTALS' in the submenu. Press the
SELECT
button reset all accumulated totals for water and
foam. Confirm action with
SELECT
button when dialog is displayed.
4. Within 10 seconds, the AccuMax system will automatically create a new incident record. ‘REPORT NEW
INCIDENT’ message will be briefly displayed in the message bar.