Mounting the Master Station
9 of 82
Publication S703E V1.1
Issue 06/09
Terminal ac
Connection
(85-265V ac)
dc Connection
(18-36V dc)
1 N
(Neutral)
0
V
2 L
(Line)
24
V
3 E
(Earth)
Earth
1.5 ESD and Alarm Output Connector
There is a removable screw terminal connector plugged into the main circuit board of the P3F master
station for the connection of ESD hard-wired inputs and for connection to the internal alarm relay
contacts, when required. (On most systems these terminals will not be used; in which case a hard-
wired link between pins 4 and 5 should be added.)
Note that the relay is shown in the ‘Alarm Active’ or ‘power removed’ position.
1.6 Current Loop Connections
A removable screw terminal connector is located in the bottom of the Current Loop Module for the
connection of the Pakscan IIE current loop to the field mounted actuators.
Terminal
Function
1 Alarm
(common)
2
Alarm (normally closed)
3
Alarm (normally open)
4 Emergency
Shutdown
5 Emergency
Shutdown
Terminal
Function
1
Port B In
2
Port B Out
3
Port B Screen
4
Port A In
5
Port A Out
6
Port A Screen
Fig 5:
Alarm/ESD connector terminal functions
Fig 6:
Current Loop connections
Alarm
5
4
1
2
3
Emergency
Shutdown
PS710
CONNECTOR
Fig 4:
Power connector terminal functions
1
2
3
Power