Because the system and browser remembers visited pages, either the Users page will come up, or
one of the previously visited Admin level pages will appear.
Click on
Masterstation Config
to enter the main system configuration page.
Modify this page to set up the master station parameters by using the drop-down menus on each
parameter. Most default values will be suitable for getting the system started, though consideration
should be made for every setting.
The Modbus address is also set on this page. Change the Modbus address to match the desired serial
communications and Modbus TCP address for access to the actuators on the current loop. It should
not be left at 240.
Fig 62: Master station Set-up page