P3F - Pakscan Master Station Technical Manual
76 of 82
Publication S703E V1.1
Issue 06/09
Reset the network (current loop) by clicking the
reset network
button. The status information will
change and show the configuration stages. Once complete, the actuator furthest from port A should be
shown on the Network Map.
Power on the next nearest actuator and reset the network again. This actuator should then appear on
the list. Continue to power on the actuators and reset the network working back towards port A until all
the actuators are connected and appear on the map.
Now connect the port B wires and disconnect the port A wires. Reset the network and check that all
the actuators are still on the map. Having verified the loop wiring and the connection of all the
actuators in both directions, finally connect the port A wires, reset the loop and all the actuators will be
ready for control.
Once the system is working with actuators connected and no loopbacks present, the diagnostic and
control pages can all be used.
6.2 Monitoring and Controlling the Actuators
The Web Browser includes the capability to control and monitor all the actuators on the Pakscan
current loop connected to the Option Module. Go to
FCU Menu
to open the page showing all the
connected actuators and their status.
Fig 65: Pakscan 2 Option Card (Loop Card) Diagnostics page showing complete loop.