Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
3-8
Non-Intrinsically safe conditions
Figure 3-10. Typical Hand-held
Communicator connection in
Non-intrinsically safe conditions
FOUNDATION FIELDBUS
ELECTRICAL
INSTALLATION
Power Supply
The transmitter requires separate power within the range 24-240 V AC or DC
0-60Hz. Tighten the terminal screws to ensure adequate contact. See “Power
Supply” on page 3-3 and Figure 3-18 on page 3-14 for additional information.
Fieldbus Voltage limits: 9 to 32 V
Current Draw: 12.5 mA
For I.S. Applications:
U
i
< 30 V
I
i
< 300 mA
P
i
< 1.3 W
C
i
= 0
μ
F
L
i
= 0 mH
5600-HART_NONIS_EXNONEX
Rosemount
5600
Hand Held
Communicator
HART
Interface
Analog instrument
and/or DCS system
F
OUNDATION
Fieldbus