Reference Manual
00809-0100-4024, Rev BA
September 2005
A-3
Rosemount 5600 Series
Electric
Power Supply
Ultra wide power supply 24-240 V AC or DC 0-60 Hz
NOTE
Minimum power required at the transmitter power terminals is 20 V.
Power Consumption
Maximum 10 W, Nominal 5 W
Outputs
Primary Output:
Alternative 1: HART + 4-20 mA current loop
(non-IS or IS option)
Alternative 2: F
OUNDATION
fieldbus (non-IS or IS option)
Secondary Outputs:
Analog 4-20 mA current loop, active or passive
(non-IS or IS option)
Output Cabling
Twisted and shielded pair; min. 0.5 mm
2
(AWG 20)
Cable Entries
3
⫻
1
/
2
inch NPT; for cable glands or conduit entries
Optional:
1
/
2
inch NPT Cable Gland Kit
Optional:
1
/
2
inch NPT/ M20 Adapters (Set of 3)
Remote 2210 Display Unit
(1)
2
⫻
M20 entries
1
⫻
M25 entry
Analog Output
Characteristics
Type
Analog 4-20 mA Current Loop, active (with power supplied by the 5600) or
passive (for external loop-supplied power)
Galvanic Isolation
> 1500 V RMS or DC
Analog Output Electrical Characteristics
See “Product Certifications” on page B-1
Range
4-20 mA
Alarm Level
Standard: Low=3.8 mA, High=22 mA or freeze,
NAMUR NE43: High=22.50 mA,
Rosemount: Low=3.75 mA
(1)
US and Canada markets are supplied with
1
/
2
-in. and
3
/
4
-in. adapters.
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......