Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
6-16
F
OUNDATION
Fieldbus
Solution #3.2
In this solution the level channel in the analog input block is used to obtain the
volume.
Table 6-11. Analog Input
Function Block Configuration for
a Radar Level Transmitter used
in Level Measurement
(Situation #3)
Figure 6-17. Function Block
Diagram for a Level Transmitter
where level output is sealed
between 0-100%
CONFIGURATION USING
THE SENSOR BUS PORT
When using a 5601 with F
OUNDATION
Fieldbus the configuration of the
transmitter is done via DeltaV or other Fieldbus Host. With the help of Device
descriptors these hosts are able to present, read, and write necessary
information and data within the transmitter and assist the user to a successful
configuration of the transmitter.
In some cases, there could be a need for a more advanced service access to
the transmitter. This is done by using the Radar Master and accessing the
data from the Sensor Bus Port, which is always readily available. Below are
instructions of how to connect this port and how to use it.
Electrical Connection
The electrical interface is RS-485 (2-wire) and the language spoken (protocol)
is Modbus.
To be able to connect to the Sensor Bus on the Rosemount 5601, you must
have a RS-232/485 converter. Below you find two models of such RS-232/485
modems which have been successfully used to communicate with the 5601
on the Sensor Bus. Basically any type of RS-232/485 converter can be used
but different Models use different switches/settings etc., and therefore they
are not listed here. The recommended type for field use is the K2.
The converter is to be connected on the Sensor Bus Port which is normally
used by the Rosemount 2210 Display Unit. Disconnect the communication
wires (X2: 6 & 7) to the Display Unit.
Parameter
Configured Values
L_TYPE
Indirect
XD_SCALE
0 to 14m
OUT_SCALE
0 to 200m
3
Channel
1 Level
Level
Measurement
AI
Function
Block
OUT_D
OUT
0 to 200m
3
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......