Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
3-6
Optional Non-intrinsically Safe Junction Box
This is the standard intrinsically safe Junction Box (EExi) fitted with an
alternative connector for connection of non-IS output if required.
Figure 3-6. Alternative
Non-intrinsically safe junction
box
1-2
Not used
3-4
Non-intrinsically safe Secondary Analog Output
A
Ground terminal (not used)
Cable shield
Connect the shield to the cable glands.
If conduit fittings are used no cable shield is used.
Connecting HART
devices
Active output (internal loop supply)
For transmitters with active output a hand-held terminal or a HART modem
can be connected as follows:
Figure 3-7. Typical hand-held
communicator active output
(primary)
A
75C
75C
X2
1
NOT
USED
2
NOT
USED
3
SO +
4
SO -
4
3
2
1
56
00
-J
B_
EEXI
E,
TH40HEAD_ED4
EEx e
5600-ANALOGOUT_ACTIVE_ED3
X1
1
2
3
4
24-240 V
DC/AC 0-60 Hz
10 W
15 VA
Junction Box
EEx e
Input Impedance
< 300 Ohm
HART
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......