Figure 4-1 illustrates how the analog output signal is related to the actual
measured product level and the specified upper and lower limits. As
illustrated, if the source signal exceeds the Upper limit or falls below the
Lower limit, the output current is set according to the specified Alarm Mode
settings.
If your transmitter is equipped with an optional analog output
(Analog Output 2), configure it as described above.
Figure 4-1. Alarm Mode Settings
Analog Output current as a function of product level for different alarm mode
settings. The shaded area indicates analog output in Alarm mode. The graphs
are valid when Disable Limit Alarm if Out of Range is not set.
Upper
Lower
3.8 mA
22 mA
20 mA
4 mA
20 mA
4 mA
20 mA
4 mA
Level
Analog
Output
Analog
Output
Analog
Output
Time
Time
Time
Time
20 mA
4 mA
Analog
Output
Time
20 mA
4 mA
Analog
Output
Time
Product Level
Alarm Mode
Low Current
Alarm Mode
High Current
Alarm Mode
Freeze Current
Alarm Mode
Binary High
Alarm Mode
Binary Low
5600_C
_02A
.E
P
S
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......