Reference Manual
00809-0100-4024, Rev BA
September 2005
7-13
Rosemount 5600 Series
2210 Display Unit
8. Select the
False Echo
option from the Custom Setup menu (optional). In
normal operation the transmitter compares detected echoes with a list of
registered
disturbance echoes, in order to decide which one is the
actual product surface. To view a list of echoes that the transmitter has
detected select the
Tank Echoes
option.
Select echoes from this list and add to the list of registered echoes. Only
register disturbing echoes which can be identified as caused by an object
in the tank. To register a disturbance echo, do the following:
a. Move the cursor to the echo you want
to add to the list.
b. Click
Edit
.
c. Move the cursor to
Add to list
, and click
Mark
.
d. Click
Save
to register the marked echo.
e. Repeat steps
a
to
d
if you wish to register more disturbance echoes.
The
Set as surface
option allows you to define an echo as the
product surface. Mark the
Add new false
option if you want to
manually add echoes.
This may be a useful option if, for example,
there are known disturbances below the product surface which can
not be detected by the transmitter at the time of installation.
f. Click
CNCL
to return to the False Echo menu. To view the current
list of registered disturbing echoes select the
Reg. False Echoes
.
To remove a registered disturbance echo, do the following
(see“Disturbance Echo Handling” on page 4-11):
a. Move the cursor to the echo you want to remove.
b. Click
Edit
.
c. Select the
Remove echo
option and click
MARK
.
d. Click
Save
to remove the selected echo.
Mark the
Add new false
option if you want to manually add a false echo to
the list of registered disturbance echoes. Mark the
Clear list
option if you
want to remove the whole list of registered disturbance echoes. This option
may be useful if you
want to create a completely new list.
9. Select the
Volume
option from the Custom Setup menu. The
Volume
option allows you to setup the 5600 transmitter for volume calculations.
You can choose between using either a predefined tank shape like a
sphere or a horizontal or vertical cylinder, or entering level and volume
values into a strapping table.
a. Select
Shape
and press
Edit.
Choose the Tank Geometry to be
used for volume calculation and press
Save
.
b. Select
Diam
and press
Edit
.
Set the tank diameter and press
Save
.
c. Select
Zero Level Offset
and press
Edit
. Set the distance from zero
level to tank bottom and press
Save
.
d. Select
Volume Offset
and press
Edit
. Set the volume offset and
press
Save
.
e. Select
Volume Control
and press
Edit
. Mark the NegVolDisabled
option and press
Save
.
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......