Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
3-14
Connecting the Rosemount 2210 Display Unit
1. For power supply connect a wire between terminal block X2, position 5
and terminal block X12, position 1.
2. For communication connect a wire between terminal block X2, position 6
and terminal block X12, position 2, and a wire between terminal block X2
position 7 and terminal block X12 position 3.
3. Finally for grounding connect a wire from the IS Ground screw in the X2
terminal compartment to terminal block X12 position 4.
Temperature
Measurement
For temperature measurements you can use 1-3 3-wire RTD spot elements or
1-6 3-wire RTDs with common return. The sensors are connected to nozzle
X17 and X18 on the optional TP40 board. Depending on the type of sensor
that is used, different jumpers must be set on nozzles X24, X25, X26, X27
and X28, see Figure 3-18, Figure 3-19, and Figure 3-20.
Figure 3-18. Overview of the
TP40 board
RDU40_TP40
C
B
A
A
B
C
X11
X12
X17
X25
X18
X24
X26
X27
X28
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4
1
2
3
4
Position 2
Position 1
C l o s e d
O p e n
2210 Display Unit
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......