Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
A-4
Accuracy
± 300
μ
A at 4 mA
± 600
μ
A at 20 mA
Resolution
0.5
μ
A (0.003%)
Linearity
±0.01%
Temperature Drift
± 28 ppm/°F (±50 ppm/°C)
Output Impedance
>10 M
Ω
Voltage Compliance
7-30 V (passive output)
External Loop Resistance
<700
Ω
(passive output with 24 V external supply)
<300
Ω
(active output)
Fieldbus Output
Characteristics
Type
Function blocks available in the device are:
• 1 Level Transducer Block
• 1 Register Transducer Block
• 6 Analog Input Blocks
Fieldbus Output Electrical Characteristics
Fieldbus Voltage limits: 9 to 32 V
Current Draw: 12.5 mA
For I.S. Applications:
U
i
< 30 V
I
i
< 300 mA
P
i
< 1.3 W
C
i
= 0
μ
F
L
i
= 0 mH
Lift-off Minimum Voltage
9.0 V
Class
Link Master (LAS)
Number of Available VCRs
20
VCR Statistics
Yes
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......