Application Example:
Radar Level Transmitter,
Level value in percent
(%)
Situation #2
The level of a tank is to be measured using the Radar Level transmitter
mounted on a nozzle on the top of the tank. The maximum level in the tank is
46ft (14m). The level value shall be displayed in percentage of the full span
(see Figure 6-13).
Figure 6-13. Situation #2
Diagram
Solution #2
Table 6-9 lists the appropriate configuration settings, and Figure 6-14
illustrates the correct function block configuration.
Table 6-9. Analog Input
Function Block Configuration for
a Level Transmitter where level
output is sealed between
0-100%
Figure 6-14. Function Block
Diagram for a Level Transmitter
where level output is sealed
between 0-100%
46 ft
(14m)
100%
0%
5600_1
1A
.EP
S
Parameter
Configured Values
L_TYPE
Indirect
XD_SCALE
0 to 14 m
OUT_SCALE
0 to 100%
CHANNEL
1 Level
Level
Measurement
AI
Function
Block
OUT_D
OUT
0 to 100%
Summary of Contents for 5600 Series
Page 2: ......
Page 4: ......
Page 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Page 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Page 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Page 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Page 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Page 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Page 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Page 209: ......