Remote Commands
R&S
®
Spectrum Rider FPH
349
User Manual 1321.1011.02 ─ 06.00
CALCulate<1...2>:LIMit<1...2>:ACPower:ALTernate<1...11>[:RELative]:STATe
<State>
This command turns the relative limit check for an alternate channels on and off.
You have to activate the general ACLR limit check before using this command with
CALCulate<1...2>:LIMit<1...2>:ACPower:STATe
The suffix at CALCulate and LIMit are irrelevant for this command.
The suffix at ALTernate selects one of the 11 alternate channels.
Parameters:
<State>
ON | OFF
*RST:
OFF
Example:
CALC:LIM:ACP:ALT3:STAT ON
Activates the relative limit check for the third alternate channel.
CALCulate<1...2>:LIMit<1...2>:ACPower:ALTernate<1...11>:ABSolute
<AbsoluteLimit>
This command defines the absolute limit for the alternate channels.
Note that the absolute limit has no effect on the limit check if it is below the relative limit
CALCulate<1...2>:LIMit<1...2>:ACPower:ALTernate<1...11>[:
on page 348). This mechanism allows automatic checking of the absolute
basic values of adjacent-channel power as defined in mobile radio standards.
The suffix at CALCulate and LIMit are irrelevant for this command.
The suffix at ALTernate selects one of the 11 alternate channels.
Parameters:
<AbsoluteLimit>
Range:
-500 dBm to 500 dBm
Default unit: dBm
Example:
CALC:LIM:ACP:ALT3:ABS -30
Sets the absolute limit to -30 dBm for the third alternate channel.
CALCulate<1...2>:LIMit<1...2>:ACPower:ALTernate<1...11>:ABSolute[:STATe]
<State>
This command turns the absolute limit check for an alternate channel on and off.
You have to activate the general ACLR limit check before using this command with
CALCulate<1...2>:LIMit<1...2>:ACPower:STATe
The suffix at CALCulate and LIMit are irrelevant for this command.
The suffix at ALTernate selects one of the 11 alternate channels.
Parameters:
<State>
ON | OFF
*RST:
OFF