Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
35
Component Test Procedures
Chapter 2
Figure 11 - Field Fuses Location
8.
Remove the cable from connector XP on the pulse transformer circuit
board. See
for connector location.
9.
Check the gate cathode junction of the field SCR/dual diode module.
With the digital multimeter set to “diode test” measure the resistance
across the modules (lead orientation is not critical). See
below.
If a low resistance is detected, replace the SCR/dual diode module. See
Field SCR and Dual Diode Module Removal and Installation on page 72
Table 11 - SCR/Dual Diode Module Gate Cathode Junction Measurements
Measure from…
To…
Nominal meter reading:
XP1
XP2
10…20
XP3
XP4
The field fuses are located on the control EMI shield next to the control board