Chapter 3
Access Procedures
11.
For Pulse Transformer boards with an armature voltage feedback terminal
block, FIR3-XX, rev. “M” and higher, remove the cable from connector
XCD_I0 on the upper right corner of the board.
12.
Remove the six screws and washers that secure the pulse transformer board
to the drive and remove the board.
Configure the Pulse Transformer Circuit Board
The new pulse transformer circuit board must be configured to match the drive
size (armature output current and HP rating). The steps required to configure
the pulse transformer board are different based on the revision code of the pulse
transformer board. See either,
Configuring a Pulse Transformer Board FIR3-xx
Configuring a Pulse Transformer Board FIR3-
xx Rev. “M” and Higher on page 69
.
XCD_IO
TO6
KGO6
T6
KG6
PE
PE1
XCD
Remove cable from XCD_IO connector
Remove screws and washers
Note: Regenerative Drive Shown