Move the EMI shield to the lowered position and remove the nuts and
washers that secure the wires (red and white) to each of the AC current
transducers and remove the wires.
14.
Remove the upper screw that secures each of the AC current transducer to
the U phase power terminal.
IMPORTANT
Note the color and location of each lead to ensure that each wire is
properly connected during installation.
Remove
nuts,
washers
and wires
Note
: Left AC current transducer of regenerative drive shown.
Remove
screw
Note
: Left AC current transducer of regenerative drive shown.