Component Test Procedures
Check the Pulse Transformer Board
The armature pulse transformer circuit board contains an isolated gate firing
circuit and also provides dv/dt protection for the armature SCR modules. A
malfunction of these devices will be indicated by either an Overcurrent fault
(F13), blown or tripped incoming protection devices or erratic motor operation.
Use the following procedure if a malfunction in this circuitry is suspected.
1.
General Safety Precautions on page 10
2.
Remove power from the drive. See
Remove Power from the Drive on
3.
Remove the pulse transformer board (see
Pulse Transformer Circuit Board
Removal and Installation on page 62
).
4.
With a digital multimeter set for a “continuity check”, measure each
connection point on the pulse transformer board listed in the tables below.
See
for connector locations.
If any of the actual measurements are out of tolerance, replace the pulse
transformer board.
Table 6 - Armature Pulse/Snubber Circuit Measurements for Regenerative Drives
Table 7 - Armature Pulse/Snubber Circuit Measurements for Non-Regenerative Drives
For SCR
Measure From
. . .
To . . .
Meter reading:
Connector XY Pinout
1
KG1
XY-4
“open circuit”
4
KG4
XY-1
2
KG2
XY-5
5
KG5
XY-2
3
KG3
XY-6
6
KG6
XY-3
01
KG01
XY-1
04
KG04
XY-4
02
KG02
XY-2
05
KG05
XY-5
03
KG03
XY-3
06
KG06
XY-6
For SCR
Measure From
. . .
To . . .
Meter reading:
Connector XY Pinout
1
KG1
XY-1
“open circuit”
4
KG4
XY-4
2
KG2
XY-2
5
KG5
XY-5
3
KG3
XY-3
6
KG6
XY-6
10
.
.
.
.
.
1
10
.
.
.
.
.
1