116
Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
Chapter 3
Access Procedures
5.
Locate the cooling fan terminal block and loosen the screws that secure the
fan power supply wires to the terminal block. The cooling fan terminal
block is located below the internal armature leg fuses and between the
phase V and W AC input bus bars.
6.
At the bottom of the drive, remove the two screws that secure the fan to
the drive frame and pull the fan away from the drive.
Loosen screws
Phase V bus bar
Armature leg fuse
Phase W bus bar
Terminal C of DC output
Remove screws