Access Procedures
Chapter 3
Armature Leg Fuses Removal
and Installation
Remove the Armature Leg Fuses
Note:
This procedure requires the use of a 17mm open ended wrench.
1.
General Safety Precautions on page 10
.
2.
Remove power from the drive. See
Remove Power from the Drive on
.
3.
Remove the covers from the drive. See
Remove the Protective Covers from
4.
Remove the two screws and washers that secure the bottom of the
transient noise filter board to the drive.
5.
Move the control EMI shield. See
Move the Control EMI Shield on
.
IMPORTANT
It is necessary to remove the transient noise filter circuit board in order
to remove the fuses from the V phase input bus bars.
Remove screws and washers