104
Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
Chapter 3
Access Procedures
11.
Temporarily lift the EMI shield and remove the screw that secures the
ground wire (from the pulse transformer board) to W phase power
terminal and remove the wire.
12.
Remove the lower screw that secures the right side AC current transducer
to the W phase power terminal.
Remove screw and wire
Remove screw and wire