Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
69
Access Procedures
Chapter 3
Total Resistance Values
Table 14 - 230V AC Input Drives
Table 15 - 460V AC Input Drives
3.
Seal the TA potentiometer in place using RV (silicon).
4.
Install the Pulse Transformer Circuit Board on page 70
Configuring a Pulse Transformer Board FIR3-xx Rev. “M” and Higher
Set DIP switches S3 and S4 (shown in the illustration below) on the pulse
transformer board to the correct settings based on the appropriate AC input
voltage, armature output current, and HP rating shown in
.
Drive Current
Rating Code
DC
Amps
AC Line
Amps
HP
Set RTA Value Using TA
Potentiometer (Ohms)
521
521
426
150
4.699
Drive Current
Rating Code
DC
Amps
AC Line
Amps
HP
Set RTA Value Using TA
Potentiometer (Ohms)
495
495
404.4
300
4.945
667
667
544.9
400
3.67