50
Rockwell Automation Publication 2711T-UM001E-EN-P - March 2019
Chapter 4
Install and Operate the Junction Boxes
M12 Dry Contact, E-stop, and Enabling Device Pin Descriptions
Mini-DIN DC Power Pin Descriptions
Connect Power to IP65 Junction Boxes
After an IP65 junction box has been mounted, configured, and wired or
connected, apply power to the junction box.
For information on 24V DC power supply requirements, see
Pin
No.
M12 Dry Contact
Pin Descriptions
Pin
No.
M12 E-stop
Pin Descriptions
Pin
No.
M12 Enabling Device
Pin Descriptions
1
External 24V input
1
E-stop 2 test output
1
Enabling device 2 test output
2
—
2
E-stop 2 safe input
2
Enabling device 2 safe input
3
Ground (GND)
3
—
3
—
4
Dry contact output
4
E-stop 1 safe input
4
Enabling device 1 safe input
5
—
5
E-stop 1 test output
5
Enabling device 1 test output
3
2
1
4
5
Pin
No.
Description
1
Power –
2
—
3
Power +
4
—
SHOCK HAZARD:
Supply the IP65 junction box and the second generation
MobileView terminal exclusively from power sources with SELV or PELV circuit
protection according to EN 61131-2.
Only connect voltages and circuits that are separated from dangerous voltages (for
example, by means of sufficient insulation) to connections, terminals or interfaces
up to a rated voltage of 50V DC.
4
1
2
3
Summary of Contents for Allen-Bradley MobileView 2711T-VMBRACKET
Page 6: ...6 Rockwell Automation Publication 2711T UM001E EN P March 2019 Table of Contents Notes ...
Page 14: ...14 Rockwell Automation Publication 2711T UM001E EN P March 2019 Chapter 1 Features Notes ...
Page 100: ...100 Rockwell Automation Publication 2711T UM001E EN P March 2019 Index Notes ...
Page 101: ...Rockwell Automation Publication 2711T UM001E EN P March 2019 101 Index Notes ...
Page 102: ...102 Rockwell Automation Publication 2711T UM001E EN P March 2019 Index Notes ...
Page 103: ......